Knowledge Centre >Sample 5 bus system for Load Flow

Reference

Elements of  Power System Analysis
By William D. Stevenson,Jr.
5 bus sample system
Ref. Figure 8.1,

Page No. : 200

ublication : McGRAW-HILL INTERNATIONAL EDITIONS

Problem  Definition :

Generators are connected at buses 1 and 3.  Loads are indicated at buses 2, 4 and 5.  Base values for the system are 100MVA, 138 kV in the high-tension lines considered here. Impedance for the six lines is given the table 8.1. Table 8.2 lists values of real, reactive power and voltage at each bus.  Voltage magnitude and angle are to be held constant at the swing bus (Bus1).

System frequency is 60 Hz.

Impedances and line charging for the sample system

Table : 8.1

Line, bus to bus

Length Km

Miles

R
ohms

X
ohms

R in p.u

X in p.u

Charging MVAR

1-2

64.4

40

8

32

0.042

0.168

4.1

1-5

48.3

30

6

24

0.031

0.126

3.1

2-3

48.3

30

6

24

0.031

0.126

3.1

3-4

 128.7

80

16

64

0.084

0.336

8.2

3-5

80.5

50

10

40

0.053

0.210

5.1

4-5

96.5

60

12

48

0.063

0.252

6.1

P, Q and V at each bus is given in Table 8.2

Table 8.2

Bus
No

Generator

Load

V per unit

Remarks
P-MW Q-Mvar P-MW Q-Mvar

1

-

-

65

30

1.04<0°

Swing bus

2

0

0

115

60

1.00<0°

Load bus(inductive)

3

180

-

70

40

1.02<0°

Voltage magnitude constant

4

0

0

70

30

1.00<0°

Load bus(inductive)

5

0

0

85

40

1.00<0°

Load bus(inductive)

Figure 8.2 Digital-Computer solution of load flow for the system of Example 8.1 Base is 100 MVA

 

Figure 8.2

Bus Code

Name

Volts

Angle

Generation
MW

Generation
MVAR

Load
MW

Load MVAR

1-2

BIRCH

1.040

0.0

234.7

100.1

65.0

30.0

1-3

ELM

0.961

-6.3

0.0

0.0

115.0

60.0

2-1

MAPLE

1.020

-3.7

180.0

110.3

70.0

40.0

2-3

OAK

0.920

-10.9

0.0

0.0

70.0

30.0

2-4

PINE

0.968

-6.2

0.0

0.0

85.0

40.0

 

LINE FLOW SWING BUS IS 1

To Bus

Bus Name

MW

MVAR

2

ELM

73.98

31.55

5

PINE

95.68

38.56

1

BIRCH

-71.41

-25.39

3

MAPLE

-43.59

-34.60

2

ELM

44.59

35.65

4

OAK

40.46

18.06

5

PINE

24.95

16.58

3

MAPLE

-38.74

-18.90

5

PINE

-31.25

-11.09

1

BIRCH

-92.59

-29.14

3

MAPLE

-24.44

-19.62

4

OAK

32.03

8.77

 

Base SLD made using MiPower

SLD with Load Flow Analysis Results